BM1964

3C X 1.50 Sqmm Fire Survival Armoured Cable, BS: 7846

Stranded Annealed Bare Copper Conductor, Double Layer of Glass Mica tape, XLPE Insulated, Cores laid-up concentrically, LSZH Inner Jacket, GI Wire Armoured and Overall LSZH Jacketed Fire Survival Armoured Cable. ART, UV, RoHS, REACH, 950°C for 3 Hours, 600/1000 V, BS: 7846 & BS: 6387 (CWZ)

Data Sheet
Suitable Applications toggle
  • Fire Alarm Systems
  • Public Address Systems
  • Fireman’s Lifts
  • Magnetic Door Hold Open Devices
  • Fire Pumps, Pressurization Systems
  • Emergency Lighting Exit Signage
  • Smoke Ventilation
    (Dampers & Actuators)
  • Fire Fighting Shafts
    (Staircase, Lift, Lift Lobby)
  • Lighting in Fire Command Centers
    and Security Rooms
  • And other Critical Equipment
Special Features toggle
  • Maintains Electrical Functionality During Fire
  • Resistance to fire at 950 Deg.C for 3 Hours
  • 90% or More Visibility during Fire & Smoke
  • Excellent Flame Retardancy Low Smoke Halogen Free
  • Excellent Crack Resistance
  • Excellent Water Resistant Properties
  • UV Resistant
  • Anti Rodent & Termite Properties
General Reference Satandards toggle
BS: 7846, BS: 6387
IEC: 60228, BS: 7655 Sec 1.3, BS: 7655 Sec 6.1
ASTM D: 2843, ASTM D: 2863, IEC: 60754-1, IEC: 60332-1
Construction and Dimensions toggle
Conductor
Material Stranded (Class 2) Annealed Bare Copper Conductor
Grade Electrolytic
Area of Conductor 1.50 Sqmm
No. of Strands As per Class 2
Diameter of Each Strand [Before Stranding] As per Class 2
Shape of Conductor Stranded and Circular
Fire Barrier Tape
Material Double Layer of Glass Mica Tape
Coverage [Min.] 100%
Thickness [Min.] 0.11 ± 0.015 mm
Insulation
Material XLPE (GP8) Compound
Type of Process Extruded
Thickness [Nom.] 0.6 mm
No. of Cores 3 Core
Cable Formation
Laid-up 3 Core Lay Up in Concentrically to form a Circular Cable
Inner Jacket
Material LSZH (LTS-1) Compound
Type of Process Extruded
Thickness [Nom.] 0.8 mm
Armouring
Material Galvanised Steel Round Wire
Layer Single Layer
Size of Armour [Nom.] 0.9 ± 0.030 mm
Outer Jacket
Material LSZH (LTS-1) Compound
Type of Process Extruded
Thickness [Nom.] 1.3 mm
Overall Cable Diameter 13.5 ± 2.0 mm
Cable Colour Code toggle
Core Identification Brown, Black and Grey
Inner Jacket Black
Outer Jacket Red
Packing and Marking toggle
Printing on Cable < AGILON > < 3C X 1.50 SQ MM > < FIRE SURVIVAL ARMOURED LSZH CABLE >
< 600/1000 V > < BS: 7846 > < BS: 6387 (CWZ) > < ART > < UV > < RoHS >
< REACH > < Year of Mfg. >
Sequential Length Marking At every one meter of interval
Standard Packing Length 1000 meters
Packing Material Packing shall be done in Non-returnable wooden drum
Tolerance on Length ±5% Tolerance
Electrical Characteristics toggle
Voltage Grade 600/1000 V
Max. DC Conductor Resistance 12.1 Ω/km at 20°C
Max. AC Conductor Resistance 15.49 Ω/km at 90°C
Min. Insulation Resistant constant 3.67 MΩ/km at 90°C ±2°C
High Voltage Test [C-C] 3.5 kVac rms for 5 Minute
Short Circuit Rating of Conductor 0.215 kA for 1 Sec
Mechanical Characteristics toggle
Maximum Conductor Temperature
Continuous Operation 90°C
During Short Circuit 250°C
Bending Radius [Min.]
During Installation 12 x OD; (Where OD is the Overall Diameter of Cable)
Fixed Installation 10 x OD; (Where OD is the Overall Diameter of Cable)
Properties Before Ageing [For Insulation]
Tensile Strength, Min. 12.5 N/mm²
Elongation at Break, Min. 200%
Properties Before Ageing [For Jacket]
Tensile Strength, Min. 10.0 N/mm²
Elongation at Break, Min. 100%
Environmental and Overall Characteristics toggle
Installation
Suitability Indoor / Outdoor
Temperature Range Fixed Installation: -20°C to +90°C
During Installation: +10°C to +80°C
Fire Resistance Test
As per BS: 6387
Resistance to Fire Alone [C] 950ºC for 3 h
Resistance to Fire with Water Spray [W] 650ºC for 30 minute Impact applied every 30 second for 15 minutes
Resistance to Fire with Mechanical Shock [Z] 950ºC for 30 minute Flame for 15 minute, Then water spray 15 min. with flame
A. C. Continuous Current Rating
Current Rating in Ground 26 Amp at @ 30°C
Current Rating in Duct 22 Amp at @ 30°C
Current Rating in Air 23 Amp at @ 40°C
LSZH Properties
and Tests
Oxygen Index ≥ 35% at 27±2°C; (When tested as per ASTM D: 2863)
Temperature Index ≥ 250°C; (When tested as per ASTM D: 2863)
HCL Gas Emission ≤ 0.5% [By weight]; (When tested as per IEC: 60754-1)
Smoke Density Rating ≤ 10%; (When tested as per ASTM D: 2843)
Flame Retardant Test IEC: 60332-1-2
Compliance
Anti Rodent & Termite Properties Yes
UV Resistance Yes
RoHS & REACH Compliant Yes
Logo1 Logo2 Logo3 Logo4 Logo5 Logo9 Logo6 Logo7 Logo8
All Rights Reserved © 2025, Agilon Cables India Private Limited
Agilon pursues publishing accurate data,unpredictable variables may result in inadvertent inaccuracies and incompleteness. The details presented herein, though reasonably verified, remain susceptible to unintentional typos or information gaps. Further, product specifications tend to frequently evolve based on ongoing research and feedback. They are subject