BM1964
3C X 1.50 Sqmm Fire Survival Armoured Cable, BS: 7846
Stranded Annealed Bare Copper Conductor, Double Layer of Glass Mica tape, XLPE Insulated, Cores laid-up concentrically, LSZH Inner Jacket, GI Wire Armoured and Overall LSZH Jacketed Fire Survival Armoured Cable. ART, UV, RoHS, REACH, 950°C for 3 Hours, 600/1000 V, BS: 7846 & BS: 6387 (CWZ)
Suitable Applications
- Fire Alarm Systems
- Public Address Systems
- Fireman’s Lifts
- Magnetic Door Hold Open Devices
- Fire Pumps, Pressurization Systems
- Emergency Lighting Exit Signage
- Smoke Ventilation
(Dampers & Actuators)
- Fire Fighting Shafts
(Staircase, Lift, Lift Lobby)
- Lighting in Fire Command Centers
and Security Rooms
- And other Critical Equipment
Special Features
- Maintains Electrical Functionality During Fire
- Resistance to fire at 950 Deg.C for 3 Hours
- 90% or More Visibility during Fire & Smoke
- Excellent Flame Retardancy Low Smoke Halogen Free
- Excellent Crack Resistance
- Excellent Water Resistant Properties
- UV Resistant
- Anti Rodent & Termite Properties
General Reference Satandards
BS: 7846, BS: 6387
IEC: 60228, BS: 7655 Sec 1.3, BS: 7655 Sec 6.1
ASTM D: 2843, ASTM D: 2863, IEC: 60754-1, IEC: 60332-1
Construction and Dimensions
Conductor
| Material | Stranded (Class 2) Annealed Bare Copper Conductor |
| Grade | Electrolytic |
| Area of Conductor | 1.50 Sqmm |
| No. of Strands | As per Class 2 |
| Diameter of Each Strand [Before Stranding] | As per Class 2 |
| Shape of Conductor | Stranded and Circular |
Fire Barrier Tape
| Material | Double Layer of Glass Mica Tape |
| Coverage [Min.] | 100% |
| Thickness [Min.] | 0.11 ± 0.015 mm |
Insulation
| Material | XLPE (GP8) Compound |
| Type of Process | Extruded |
| Thickness [Nom.] | 0.6 mm |
| No. of Cores | 3 Core |
Cable Formation
| Laid-up | 3 Core Lay Up in Concentrically to form a Circular Cable |
Inner Jacket
| Material | LSZH (LTS-1) Compound |
| Type of Process | Extruded |
| Thickness [Nom.] | 0.8 mm |
Armouring
| Material | Galvanised Steel Round Wire |
| Layer | Single Layer |
| Size of Armour [Nom.] | 0.9 ± 0.030 mm |
Outer Jacket
| Material | LSZH (LTS-1) Compound |
| Type of Process | Extruded |
| Thickness [Nom.] | 1.3 mm |
| Overall Cable Diameter | 13.5 ± 2.0 mm |
Cable Colour Code
| Core Identification | Brown, Black and Grey |
| Inner Jacket | Black |
| Outer Jacket | Red |
Packing and Marking
| Printing on Cable |
< AGILON > < 3C X 1.50 SQ MM > < FIRE SURVIVAL ARMOURED LSZH CABLE > < 600/1000 V > < BS: 7846 > < BS: 6387 (CWZ) > < ART > < UV > < RoHS > < REACH > < Year of Mfg. > |
| Sequential Length Marking | At every one meter of interval |
| Standard Packing Length | 1000 meters |
| Packing Material | Packing shall be done in Non-returnable wooden drum |
| Tolerance on Length | ±5% Tolerance |
Electrical Characteristics
| Voltage Grade | 600/1000 V |
| Max. DC Conductor Resistance | 12.1 Ω/km at 20°C |
| Max. AC Conductor Resistance | 15.49 Ω/km at 90°C |
| Min. Insulation Resistant constant | 3.67 MΩ/km at 90°C ±2°C |
| High Voltage Test [C-C] | 3.5 kVac rms for 5 Minute |
| Short Circuit Rating of Conductor | 0.215 kA for 1 Sec |
Mechanical Characteristics
Maximum Conductor Temperature
| Continuous Operation | 90°C |
| During Short Circuit | 250°C |
Bending Radius [Min.]
| During Installation | 12 x OD; (Where OD is the Overall Diameter of Cable) |
| Fixed Installation | 10 x OD; (Where OD is the Overall Diameter of Cable) |
Properties Before Ageing [For Insulation]
| Tensile Strength, Min. | 12.5 N/mm² |
| Elongation at Break, Min. | 200% |
Properties Before Ageing [For Jacket]
| Tensile Strength, Min. | 10.0 N/mm² |
| Elongation at Break, Min. | 100% |
Environmental and Overall Characteristics
Installation
| Suitability | Indoor / Outdoor |
| Temperature Range |
Fixed Installation: -20°C to +90°C During Installation: +10°C to +80°C |
Fire Resistance Test
As per BS: 6387
As per BS: 6387
| Resistance to Fire Alone [C] | 950ºC for 3 h |
| Resistance to Fire with Water Spray [W] | 650ºC for 30 minute Impact applied every 30 second for 15 minutes |
| Resistance to Fire with Mechanical Shock [Z] | 950ºC for 30 minute Flame for 15 minute, Then water spray 15 min. with flame |
A. C. Continuous Current Rating
| Current Rating in Ground | 26 Amp at @ 30°C |
| Current Rating in Duct | 22 Amp at @ 30°C |
| Current Rating in Air | 23 Amp at @ 40°C |
LSZH Properties
and Tests
and Tests
| Oxygen Index | ≥ 35% at 27±2°C; (When tested as per ASTM D: 2863) |
| Temperature Index | ≥ 250°C; (When tested as per ASTM D: 2863) |
| HCL Gas Emission | ≤ 0.5% [By weight]; (When tested as per IEC: 60754-1) |
| Smoke Density Rating | ≤ 10%; (When tested as per ASTM D: 2843) |
| Flame Retardant Test | IEC: 60332-1-2 |
Compliance
| Anti Rodent & Termite Properties | Yes |
| UV Resistance | Yes |
| RoHS & REACH Compliant | Yes |
All Rights Reserved © 2025, Agilon Cables India Private Limited
Agilon pursues publishing accurate data,unpredictable variables may result in inadvertent inaccuracies and incompleteness. The details presented herein, though reasonably verified, remain susceptible to unintentional typos or information gaps. Further, product specifications tend to frequently evolve based on ongoing research and feedback. They are subject