• Building Management & Security System Cables
  • Fire Survival Cables
  • Industrial Automation Cables
  • Bus System Cables
  • Instrumentation Cables
  • Rubber Electrical Cables
  • Marine & Offshore Cables
  • High Temperature Cables
  • PUR Cables
  • Signal & Control Cables
  • Single & Multicore Flexible Cables
  • Thermocouple Cables
  • Coaxial Cable

Main Image
BM2032

2C X 2.50 Sqmm Fire Survival LSZH Cable

Stranded Annealed Bare Copper Conductor, Double Layer Glass Mica taped, XLPE Insulated, Cores laid-up concentrically and Overall LSZH Jacketed Fire Survival LSZH Cable. ART, UV, RoHS, REACH, 300/500 V, BS: 7629-1, BS EN: 50200 PH60

Data Sheet
General Reference Standards toggle
BS: 7629-1, BS EN: 50200 PH60
IEC: 60228, BS: 7655 Sec 1.3, BS: 7655 Sec 6.1
ASTM D: 2843, ASTM D: 2863, IEC: 60754-1, IEC: 60332-1
Construction and Dimensions toggle
Conductor
Material Stranded (Class 2) Annealed Bare Copper Conductor
Grade Electrolytic
Area of Conductor 2.50 Sqmm
No. of Strands As per Class 2
Diameter of Each Strand [Before Stranding] As per Class 2
Shape of Conductor Stranded and Circular
Fire Barrier Tape
Material Double layer of Glass Mica Tape
Type of Process Helically
Coverage [Min.] 100%
Thickness [Min.] 0.11 ± 0.015 mm
Insulation
Material XLPE Compound
Type of Process Extruded
Thickness [Nom.] 0.7 mm
No. of Cores 2 Core
Cable Formation
Laid-up 2 Core Lay Up in Concentrically to form a Circular Cable
Outer Jacket
Material LSZH Compound
Type of Process Extruded
Thickness [Nom.] 1.0 mm
Overall Cable Diameter 10.5 ± 2.0 mm
Cable Colour Coded toggle
Core Identification Brown and Blue
Outer Jacket Red
Packing and Marking toggle
Printing on Cable < AGILON > < 2C X 2.50 SQ MM > < FIRE SURVIVAL LSZH CABLE > < 300/500 V > < BS EN: 50200 PH60 > < ART > < RoHS > < REACH > < Year >
Sequential Length Marking At every one meter of interval
Standard Packing Length 500 meters
Packing Material Packing shall be done in coils
Tolerance on Length ±5% Tolerance
Electrical Characteristics toggle
Voltage Grade 300/500 V
Max. DC Conductor Resistance 7.41 Ω/km at 20°C
Max. AC Conductor Resistance 9.48 Ω/km at 20°C
Min. Insulation Resistant constant 3.67 MΩ/km at 90°C±2°C
High Voltage Test [C-C] 2 kVac (rms) for 1 minute
Mechanical Characteristics toggle
Maximum Conductor Temperature
Continuous Operation 90°C
During Short Circuit 250°C
Bending Radius [Min.]
During Installation 12 x OD; (Where OD is the Overall Diameter of Cable)
Fixed Installation 10 x OD; (Where OD is the Overall Diameter of Cable)
Properties Before Ageing (For Insulation)
Tensile Strength, Min. 12.5 N/mm²
Elongation at Break, Min. 200%
Properties Before Ageing (For Jacket)
Tensile Strength, Min. 10.0 N/mm²
Elongation at Break, Min. 100%
Environmental and Overall Characteristics toggle
Installation
Suitability Indoor
Temperature Range Fixed Installation: -20 °C to +90 °C
During Installation: +10 °C to +60 °C
Fire Survival Test
Category Standard 60 EN 50200 PH60 (Annex E)
LSZH Properties and Tests
Oxygen Index ≥ 39% at 27±2°C; (When tested as per ASTM D: 2863)
Temperature Index ≥ 250°C; (When tested as per ASTM D: 2863)
HCL Gas Emission ≤ 0.3% [By weight]; (When tested as per IEC: 60754-1)
Smoke Density Rating ≤ 10%; (When tested as per ASTM D: 2843)
Flame Retardant Test IEC: 60332-1-2
Compliance
Anti Rodent & Termite Properties Yes
UV Resistance Yes
RoHS & REACH Compliant Yes
Logo1 Logo2 Logo3 Logo4 Logo5 Logo6 Logo7 Logo8 Logo9
All Rights Reserved © 2025, Agilon Cables India Private Limited
Agilon pursues publishing accurate data,unpredictable variables may result in inadvertent inaccuracies and incompleteness. The details presented herein, though reasonably verified, remain susceptible to unintentional typos or information gaps. Further, product specifications tend to frequently evolve based on ongoing research and feedback. They are subject