BM1704

2C X 1.50 Sqmm Control BMS Armoured FRLSH Cable

Stranded Annealed Bare Copper Conductor, XLPE Insulated, Cores laid-up concentrically, PVC Inner Jacket, GI Wire Armoured and Overall FRLSH PVC Jacketed Control BMS Armoured FRLSH Cable. 1100 V

Data Sheet
General Reference Standards toggle
BS: 5467, IS: 7098-1
IS: 8130, IS: 5831, IS: 3975
ASTM D: 2843, ASTM D: 2863, IEC: 60754-1, IEC: 60332-1-2
Construction and Dimensions toggle
Conductor
Material Stranded (Class 2) Annealed Bare Copper Conductor
Grade Electrolytic
Area of Conductor 1.50 Sqmm
No. of Strands As per Class 2
Diameter of Each Strand [Before Stranding] As per Class 2
Shape of Conductor Stranded and Circular
Insulation
Material XLPE Compound
Type of Process Extruded
Thickness [Min.] 0.44 mm
No. of Cores 2 Core
Cable Formation
Laid-up 2 Core Lay Up in Concentrically to form a Circular Cable
Inner Jacket
Material PVC Type ST2 Compound
Type of Process Extruded
Thickness [Min.] 0.3 mm
Armouring
Material Galvanized Steel Round Wire
Layer Single Layer
Size of Armour [Nom.] 0.90 ± 0.030 mm
Outer Jacket
Material FRLSH PVC Type ST2 Compound
Type of Process Extruded
Thickness [Min.] 1.24 mm
Overall Cable Diameter 10.2 ± 2.0 mm
Cable Colour Code toggle
Core Identification Red and Black
Inner Jacket Black
Outer Jacket Black
Packing and Marking toggle
Printing on Cable < AGILON > < 2C X 1.50 SQ MM > < CONTROL BMS ARMOURED FRLSH CABLE > < 1100 V > < 2XWY > < Year >
Sequential Length Marking At every one meter of interval
Standard Packing Length 500 meters
Packing Material Packing shall be done in coils
Tolerance on Length ±5% Tolerance
Electrical Characteristics toggle
Voltage Grade 1100 V
Max. DC Conductor Resistance 12.1 Ω/km at 20°C
Max. AC Conductor Resistance 15.49 Ω/km at 90°C
Volume Resistivity [Min.] 1 x 10¹⁴ Ohm-cm at 27°C
1 x 10¹² Ohm-cm at 90°C
High Voltage Test [C-C] 2 kVac rms for 1 Minute
Short Circuit Rating of Conductor 0.215 kA for 1 Sec
Mechanical Characteristics toggle
Maximum Conductor Temperature
Continuous Operation 90°C
During Short Circuit 250°C
Bending Radius [Min.]
During Installation 12 x OD; (Where OD is the Overall Diameter of Cable)
Fixed Installation 10 x OD; (Where OD is the Overall Diameter of Cable)
Properties Before Ageing [For Insulation]
Tensile Strength, Min. 12.5 N/mm²
Elongation at Break, Min. 200%
Properties Before Ageing [For Jacket]
Tensile Strength, Min. 12.5 N/mm²
Elongation at Break, Min. 150%
Environmental and Overall Characteristics toggle
Installation
Suitability Indoor / Outdoor
Temperature Range Fixed Installation: -20°C to +90°C
During Installation: +10°C to +80°C
FRLSH Properties
and Tests
Oxygen Index ≥ 29% at 27±2°C; (When tested as per ASTM D: 2863)
Temperature Index ≥ 250°C; (When tested as per ASTM D: 2863)
HCL Gas Emission ≤ 20% [By weight]; (When tested as per IEC: 60754-1)
Smoke Density Rating ≤ 60%; (When tested as per ASTM D: 2843)
Flame Retardant Test IEC: 60332-1-2
Logo1 Logo2 Logo3 Logo8
All Rights Reserved © 2025, Agilon Cables India Private Limited
Agilon pursues publishing accurate data,unpredictable variables may result in inadvertent inaccuracies and incompleteness. The details presented herein, though reasonably verified, remain susceptible to unintentional typos or information gaps. Further, product specifications tend to frequently evolve based on ongoing research and feedback. They are subject