BM2436
10C X 1.50 Sqmm Shielded BMS FRLSH Cable
Flexible Annealed Bare Copper Conductor, PVC Insulated, Cores laid-up concentrically, Overall Shielded with Aluminium-Mylar tape in contact with ATC Drain Wire and Overall FRLSH PVC Jacketed Shielded BMS FRLSH Cable. ART, RoHS, REACH, 300/500 V, BS EN: 50288-7
No Data Sheet Available
Suitable Applications
- Security Systems
- Burglar Alarm
- Intercom / PA-System
- Cabinet / Panel Wiring
- Power Limited Circuits
- Voice Communications
- Noisy Environment
- Control Digital Signals
- Suitable for Upto 500 V Applications
Special Features
- EMI / RFI Protection
- Anti Rodent & Termite Properties
- RoHS & REACH Compliant
- Passes IEC: 60332-1, Flame Rating
General Reference Standards
BS EN: 50288-7
IEC: 60228, IS: 5831
ASTM D: 2843, ASTM D: 2863, IEC: 60754-1, IEC: 60332-1
Construction and Dimensions
Conductor
| Material | Flexible (Class 5) Annealed Bare Copper Conductor |
| Grade | Electrolytic |
| Area of Conductor | 1.50 Sqmm |
| No. of Strands | As per Class 5 |
| Diameter of Each Strand [Before Stranding] | As per Class 5 |
| Shape of Conductor | Flexible and Circular |
Insulation
| Material | PVC Compound |
| Type of Process | Extruded |
| Thickness [Min.] | 0.44 mm |
| No. of Cores | 10 Core |
Cable Formation
| Laid-up | 10 Core Lay Up in Concentrically to form a Circular Cable |
Overall Shielding
| Material | Aluminium-Mylar Tape |
| Type | Helically |
| Thickness [Min.] | 0.032 mm |
| Overlap/Coverage [Min.] | 25% / 100% |
| Binder Tape [If required] | Polyester tape shall be provided Below and/or Over Shielding |
Drain Wire
| Material | Annealed Tinned Copper (ATC) |
| Place | Laid longitudinally, In contact with metallic side of Al-Mylar tape |
| Area of Drain Wire | 0.50 Sqmm |
Outer Jacket
| Material | FRLSH PVC Compound |
| Type of Process | Extruded |
| Thickness [Nom.] | 1.1 mm |
| Overall Cable Diameter | 12.9 ± 2.0 mm |
Cable Colour Code
| Core Colour | White with numbering |
| Outer Jacket Colour | Blue |
Packing and Marking
| Printing on Cable |
< AGILON > < 10C X 1.50 SQ MM > < SHIELDED BMS FRLSH CABLE > < 300/500 V > < ART > < RoHS > < REACH > < Year > |
| Sequential Length Marking | At every one meter of interval |
| Standard Packing Length | 300 / 500 meters |
| Packing Material | Packing shall be done in coils |
| Tolerance on Length | ±5% Tolerance |
Electrical Characteristics
| Max. DC Conductor Resistance | 13.3 Ω/km at 20°C |
| Min. Insulation Resistance | 10 MΩ/km at 20°C |
| Max. Mutual Capacitance [C-C] | 250 pf/m at 1 KHz |
| Max. Mutual Capacitance [C-S] | 450 pf/m at 1 KHz |
| Max. L/R Ratio | 40 μH/Ω |
| High Voltage Test [C-C] | 2 kVac (rms) for 1 minute |
Mechanical Characteristics
Maximum Conductor Temperature
| Continuous Operation | 70°C |
| During Short Circuit | 160°C |
Bending Radius [Min.]
| During Installation | 12 x OD; (Where OD is the Overall Diameter of Cable) |
| Fixed Installation | 10 x OD; (Where OD is the Overall Diameter of Cable) |
Properties Before Ageing [For Insulation]
| Tensile Strength, Min. | 10.0 N/mm² |
| Elongation at Break, Min. | 150% |
Properties Before Ageing [For Jacket]
| Tensile Strength, Min. | 10.0 N/mm² |
| Elongation at Break, Min. | 150% |
Environmental and Overall Characteristics
Installation
| Suitability | Indoor |
| Temperature Range |
Fixed Installation: -15°C to +70°C During Installation: +10°C to +60°C |
FRLSH Properties
and Tests
and Tests
| Oxygen Index | ≥ 30% at 27±2°C; (When tested as per ASTM D: 2863) |
| Temperature Index | ≥ 250°C; (When tested as per ASTM D: 2863) |
| HCL Gas Emission | ≤ 20% [By weight]; (When tested as per IEC: 60754-1) |
| Smoke Density Rating | ≤ 60%; (When tested as per ASTM D: 2843) |
| Flame Retardant Test | IEC: 60332-1-2 |
Compliance
| Anti Rodent & Termite Properties | Yes |
| RoHS & REACH Compliant | Yes |
All Rights Reserved © 2025, Agilon Cables India Private Limited
Agilon pursues publishing accurate data,unpredictable variables may result in inadvertent inaccuracies and incompleteness. The details presented herein, though reasonably verified, remain susceptible to unintentional typos or information gaps. Further, product specifications tend to frequently evolve based on ongoing research and feedback. They are subject
to modifications without explicit advance intimations or obligations Also note that Drawings/Images are intended for illustration purposes only and actual product may be vary.